Progressive-disclosure workflow for OpenDSS distribution-feeder studies. Use whenever the user wants to compile a DSS model, solve a distribution circuit, inspect feeder bus voltages or power, sweep load multipliers, or run daily / harmonic studies through PowerMCP — even when they just say 'solve t

License 许可
MIT
最近更新
2026-11-09
Stars
★ 0
Forks
0

01 前言 Front Matter

name
opendss
risk
low
source
https://github.com/Power-Agent/PowerSkills
license
MIT
version
1.0.0
category
electrical-engineering
description
Progressive-disclosure workflow for OpenDSS distribution-feeder studies. Use whenever the user wants to compile a DSS model, solve a distribution circuit, inspect feeder bus voltages or power, sweep load multipliers, or run daily / harmonic studies through PowerMCP — even when they just say 'solve t
imported_at
2026-09-20
source_path
powerskills-tool/skills/opendss/SKILL.md
source_repository
Power-Agent/PowerSkills
disable-model-invocation
false

03 SKILL.md 正文

OpenDSS workflow

Start with a solved feeder. Do not jump to daily or harmonic studies until the base feeder compiles and the voltage profile is understood.

Default tool ladder

  1. compile_and_solve(dss_file) to load and solve the circuit.
  2. get_total_power() and get_bus_voltages() to confirm the base operating point.
  3. set_load_multiplier(load_mult) for simple scenario sweeps.
  4. run_daily_energy_meter(meter_name, hours) for daily feeder behavior.
  5. get_harmonic_results(load_name, harmonic) only after the harmonic question is well scoped.

Working rules

  • Fix compile or solve errors before any scenario analysis.
  • For voltage issues, inspect the weak buses first.
  • Separate load-growth screening from harmonic analysis; they answer different questions.
  • Keep feeder, meter, and load names explicit in the response.

Escalation triggers

Quote the weak bus + voltage or the loaded element rather than saying "there is a problem".

Observation Escalate to
get_bus_voltages shows pu outside the feeder band (e.g. < 0.95 or > 1.05) voltage-violation-mitigation
A line, transformer, or regulator loaded above its rating thermal-overload-mitigation
compile_and_solve succeeds to compile but the solution diverges convergence-failure-mitigation
The study is DER (PV, storage) integration or hosting capacity on the feeder der-hosting-capacity-mitigation

Deliver

  • The compiled feeder and base-case status.
  • The voltage or power quantities checked.
  • Any scenario result and whether mitigation is needed.