AGENT SKILL

dc-power-flow

Build and use the DC power-flow model (B matrix, slack angle, line flows, and thermal limits) with correct MATPOWER bus-number mapping.

License 许可
Apache-2.0
最近更新
2026-11-14
Stars
★ 0
Forks
1

01 前言 Front Matter

name
dc-power-flow
description
Build and use the DC power-flow model (B matrix, slack angle, line flows, and thermal limits) with correct MATPOWER bus-number mapping.

02 资源文件 1

03 SKILL.md 正文

Steps

  1. Create a bus-number → 0‑indexed row mapping (bus numbers may be non-contiguous):
    bus_num_to_idx = {int(bus[i,0]): i for i in range(n_bus)}
    
  2. Build the nodal susceptance matrix B from in-service branches using X = branch[:,3]:
    B = np.zeros((n_bus, n_bus))
    for br in branches:
        f = bus_num_to_idx[int(br[0])]
        t = bus_num_to_idx[int(br[1])]
        x = br[3]
        if x != 0:
            b = 1.0/x
            B[f,f] += b; B[t,t] += b
            B[f,t] -= b; B[t,f] -= b
    
  3. Add a slack bus angle reference (MATPOWER bus type 3):
    slack_idx = next(i for i in range(n_bus) if int(buses[i,1]) == 3)
    constraints.append(theta[slack_idx] == 0)
    
  4. Enforce nodal DC balance (in per-unit, consistent with Pg_pu and Pd/baseMVA): [ Pg_i - Pd_i = B_{i,:},\theta ]
  5. Compute branch flow (MW) for reporting:
    b = 1.0/br[3]
    flow_MW = b*(theta[f]-theta[t]) * baseMVA
    
  6. Enforce branch thermal limits (RATE_A is branch[:,5]) as linear constraints:
    rate = br[5]
    flow = b*(theta[f]-theta[t]) * baseMVA
    constraints += [flow <= rate, flow >= -rate]
    

Expected Result

A consistent DC network model where bus angles determine line flows, thermal limits can bind, and flows/loading can be computed in MW/%.